Function modules   
8.8 Basic positioner 
  Drive functions 
524  Function Manual, 11/2017, 6SL3097-4AB00-0BP5 
The probe pulse is used to supply connector input p2660 (referencing measured value) with 
the measured value via parameter r2523. The validity of the measurement is reported to 
binector input p2661 (measurement valid feedback) via r2526.2. 
 
Note 
The following must always apply to the "Flying referencing mode" windows:
 
p2602 (outer window) > p2601 (inner window).
 
You can obtain more information on the "Flying referencing" function in the SINAMICS 
S120/S150 List Manual in funct
ion diagram 3614. 
The following then happens: 
●  If the drive has not yet been referenced, status bit r2684.11 (reference point set) is set to 
"1". 
●  If the drive has already been referenced, status bit r2684.11 (reference point set) is not 
reset when starting flying referencing. 
●  If the drive has already been referenced and the position difference is less than the inner 
window (p2601), the old actual position value is retained. 
●  If the drive has already been referenced and the position difference is more than the outer 
window (p2602), alarm A07489 (reference point offset outside window 2) is output and 
the status bit r2684.3 (pressure mark outside window 2) set. No offset to the actual 
position value is undertaken. 
●  If the drive has already been referenced and the position difference is more than the inner 
window (p2601) and less that the outer window (p2602), the actual position value is 
offset. 
 
-the-fly referencing is superimposed on an active operating mode, it is therefore not an 
 
trast to reference point approach, flying referencing can be carried out superimposed 
 
As standard, for flying referencing, measuring probe evaluation is used; when enabled, the 
measuring probe is selected (p2510) and the edge evalua
tion (p2511) (in the factory setting, 
measuring probe 1 is always the measuring probe, flank evaluation in the factory setting is 
always the 0/1 edge).