Monitoring functions and protective functions
9.5 Thermal motor protection
Drive functions
654 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
r4620[0...3] -200° C means:
a KTY84/PT1000 is connected
the temperature display is valid.
r4620[0...3] = -200° C means:
a PTC or a bimetal NC contact is connected
there is a temperature sensor fault
the sensor channel is deactivated
the temperature evaluation is deactivated
KTY84
p4100[0...3] = 2 assigns the temperature sensor type KTY84 to a corresponding channel
1 to 4, and activates the evaluation.
r4105[0...3] displays the actual temperature value of the measuring channel involved of
the temperature evaluation. If no sensor has been selected or if the actual temperature
value is invalid, the value -300° C is in the parameter.
PT1000
p4100[0...3] = 6 assigns the temperature sensor type PT1000 to a corresponding channel
1 to 4, and activates the evaluation.
r4105[0...3] displays the actual temperature value of the measuring channel involved of
the temperature evaluation. If no sensor has been selected or if the actual temperature
value is invalid, the value -300° C is in the parameter.
PTC
p4100[0...3] = 1 sets temperature sensor type PTC to the corresponding channel 1 to 4,
and activates the evaluation.
r4105[0...3] displays the actual temperature value of the temperature evaluation.
If the actual temperature value is lower than the rated response temperature, then
r4105[0...3] is set to -50° C.
If the actual temperature value is higher than the rated response temperature, then
r4105[0...3] is set to 250° C.
If no sensor has been selected or if the actual temperature value is invalid, then
r4105[0...3] is set to -300° C.