Communication
11.1 Communication according to PROFIdrive
Drive functions
764 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Notes relating to the parameter request:
Request reference:
The value is selected at random from the valid value range. The request reference
establishes the relationship between request and response.
Request ID:
02 hex → This identifier is required for a write request.
Axis:
02 hex → The parameters are written to drive 2.
Number of parameters
04 hex → The multi-parameter request comprises four individual parameter requests.
1st parameter address ... 4. Parameter address
Attribute:
10 hex → The parameter values are to be written.
Number of elements
01 hex → One array element is written.
Parameter number
Specifies the number of the parameter to be written (p1055, p1056, p1058, p1059).
Subindex:
0 dec → ID of the first array element.
1st parameter value ... 4th Parameter value
Format:
07 hex → Data type, unsigned32
08 hex → Data type, floating point
Number of values:
01 hex → A value is written to each parameter in the specified format.
Value:
BICO input parameter: Enter signal source
Adjustable parameter: Enter value
Initiate parameter request.