Par. No. Name Range  Default Unit
P0013[16] User defined parameter 0 - 65535 0 --
Defines a limited set of parameters to which the end user will have access right.
Index:.
P0013[0] 1st user parameter
P0013[1] 2nd user parameter
…
P0013[15] 16th user parameter
Dependency:
To prevent changes to user-defined parameter, set P0011 ("lock") to a different value than P0012 ("key"). 
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter 
(and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock")
Note:
● Alternatively, set P0970 = 48 (factory reset) to perform a factory reset of all parameters and selected 
connection macro or set P0970 = 49 (factory reset) to perform a factory reset of all parameters (except 
parameters for quick motor data settings) and selected connection macro.
● The default values of P0011 ("lock") and P0012 ("key") are the same
r0018[2] Inverter version display -- -- --
Displays firmware version number of the inverter or the operator panel
r0018[0]: Inverter firmware version
r0018[1]: Firmware version of the operator panel
r0024 Actual Inverter output frequency -- -- Hz
Displays actual output frequency. Slip compensation, resonance damping and frequency limitation are 
included.
r0025 Actual output voltage -- -- V
Displays [rms] voltage applied to motor.
r0026 Actual DC-link voltage -- -- V
Displays DC-link voltage.
r0027 Actual output current -- -- A
Displays [rms] value of motor current [A].
r0037 Inverter temperature [°C] -- -- °C
Displays internal inverter heatsink temperature.
Parameter list
SINAMICS V10