EasyManua.ls Logo

Siemens SINAMICS V10 - User Defined Parameter Settings

Siemens SINAMICS V10
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Par. No. Name Range Default Unit
P0013[16] User defined parameter 0 - 65535 0 --
Defines a limited set of parameters to which the end user will have access right.
Index:.
P0013[0] 1st user parameter
P0013[1] 2nd user parameter
P0013[15] 16th user parameter
Dependency:
To prevent changes to user-defined parameter, set P0011 ("lock") to a different value than P0012 ("key").
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter
(and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock")
Note:
Alternatively, set P0970 = 48 (factory reset) to perform a factory reset of all parameters and selected
connection macro or set P0970 = 49 (factory reset) to perform a factory reset of all parameters (except
parameters for quick motor data settings) and selected connection macro.
The default values of P0011 ("lock") and P0012 ("key") are the same
r0018[2] Inverter version display -- -- --
Displays firmware version number of the inverter or the operator panel
r0018[0]: Inverter firmware version
r0018[1]: Firmware version of the operator panel
r0024 Actual Inverter output frequency -- -- Hz
Displays actual output frequency. Slip compensation, resonance damping and frequency limitation are
included.
r0025 Actual output voltage -- -- V
Displays [rms] voltage applied to motor.
r0026 Actual DC-link voltage -- -- V
Displays DC-link voltage.
r0027 Actual output current -- -- A
Displays [rms] value of motor current [A].
r0037 Inverter temperature [°C] -- -- °C
Displays internal inverter heatsink temperature.
Parameter list
SINAMICS V10
80 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)

Table of Contents