[7sj6x_ueberlastschutz-150502-kn, 1, en_US]
Figure 2-42
Logic diagram of the overload protection
Setting Notes
General
The overload protection is only in effect and accessible if address 142 49 = No ambient temp or = With
amb. temp. during configuration. If the function is not required Disabled is set.
2.7.2
Functions
2.7 Thermal Overload Protection 49
SIPROTEC 4, 7SJ61, Manual 115
C53000-G1140-C210-6, Edition 05.2016