Service Conditions
The protective device is designed for use in an industrial environment and an electrical utility environment.
Proper installation procedures should be followed to ensure electromagnetic compatibility (EMC).
In addition, the following is recommended:
•
All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the numerical protec-
tive device should, as a rule, be equipped with suitable surge suppression components.
•
For substations with operating voltages of 100 kV and above, all external cables should be shielded with
a conductive shield grounded at both ends. For substations with lower operating voltages, no special
measures are normally required.
•
Do not withdraw or insert individual modules or boards while the protective device is energized. In with-
drawn condition, some components are electrostatically endangered; during handling the ESD stand-
ards (for Electrostatic Sensitive Devices) must be observed. They are not endangered when inserted into
the case.
Certifications
UL listing UL recognition
7SJ61**-*B***-**** Models with
threaded terminals
7SJ61**-*D***-**** Models with
plug-in terminals
7SJ61**-*E***-****
Design
Housing
7XP20
Dimensions See dimensional drawings, Section 4.22 Dimensions
Device Housing Size Weight
7SJ610/1/2*-*B for panel surface mounting
1
/
3
4.5 kg
7SJ610/1/2*-*D/E for panel flush mounting
1
/
3
4 kg
7SJ613/4*-*B for panel surface mounting
1
/
2
7.5 kg
7SJ613/4*-*D/E for panel flush mounting
1
/
2
6.5 kg
Protection class acc. to IEC 60529
For surface mounting housing equipment IP 51
In flush mounted housing
Front IP 51
Rear IP 50
For personal protection IP 2x with cover cap
UL conditions “For use on a Flat Surface of a Type 1 Enclosure”
4.1.8
4.1.9
4.1.10
Technical Data
4.1 General Device Data
SIPROTEC 4, 7SJ61, Manual 289
C53000-G1140-C210-6, Edition 05.2016