[sj61-web-betrmess, 1, en_US]
Figure 2-83 Measured values in the Web Monitor - examples for measured values
The currents, voltages and their phase angles derived from the primary and secondary measured values are
graphically displayed as phasor diagrams (see Figure 2-146). In addition to phasor diagrams of the measured
values, the numerical values as well as frequency and device address are indicated.
[sj61-web-phasor, 1, en_US]
Figure 2-84 Phasor diagram of the primary measured values - example
The following types of messages can be retrieved and displayed with the Web Monitor.
•
Operational messages (buffer: event log),
•
Fault messages (buffer: trip log),
•
Ground fault messages,
•
Spontaneous messages.
You can print these lists with the “Print event buffer” button.
Setting Notes
The parameters for the Web Monitor can be set separately via the device menu (Setup/Options/IP Configura-
tion) or via DIGSI for the front operator interface and for the rear service interface. These are IP addresses
related to the interface via which communication with the PC and the Web monitor is to be performed.
The IP addresses apply to SIPROTEC for the following operations via the
•
front operator interface: 192.168.1.1
•
rear service interface: 192.168.2.1
2.17.9.5
Functions
2.17 Auxiliary Functions
SIPROTEC 4, 7SJ61, Manual 217
C53000-G1140-C210-6, Edition 05.2016