Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
0 FLEXIBLE FUNC. OFF
ON
Alarm Only
OFF Flexible Function
0 OPERRAT. MODE 3-phase
1-phase
no reference
3-phase Mode of Operation
0 BLK f out of r YES
NO
YES Block while Freq. is out of
range
0 MEAS. QUANTITY Please select
Current
dV/dt rising
dV/dt falling
Binary Input
Please select Selection of Measured
Quantity
0 MEAS. METHOD Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental Selection of Measurement
Method
0 PICKUP WITH Exceeding
Dropping below
Exceeding Pickup with
0 CURRENT Ia
Ib
Ic
In
In sensitive
In2
Ia Current
0 P.U. THRESHOLD 1A 0.03 .. 40.00 A 2.00 A Pickup Threshold
5A 0.15 .. 200.00 A 10.00 A
0 P.U. THRESHOLD 1A 0.03 .. 40.00 A 2.00 A Pickup Threshold
5A 0.15 .. 200.00 A 10.00 A
0 P.U. THRESHOLD 0.001 .. 1.500 A 0.100 A Pickup Threshold
0 P.U. THRESHOLD 2.0 .. 200.0 V 110.0 V Pickup Threshold
0 P.U. THRESHOLD 1A 0.5 .. 10000.0 VAR 200.0 VAR Pickup Threshold
5A 2.5 .. 50000.0 VAR 1000.0 VAR
0 P.U. THRESHOLD 15 .. 100 % 20 % Pickup Threshold
0 P.U. THRESHOLD 4 .. 100 V/s 60 V/s Pickup Threshold
0 T TRIP DELAY 0.00 .. 3600.00 sec 1.00 sec Trip Time Delay
0A T DROPOUT DELAY 0.00 .. 60.00 sec 0.00 sec Dropout Time Delay
0A DROPOUT RATIO 0.70 .. 0.99 0.95 Dropout Ratio
0A DROPOUT RATIO 1.01 .. 3.00 1.05 Dropout Ratio
2.13.3
Functions
2.13 Flexible Protection Functions
180 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016