Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr. Parameter Function C Setting Options Default Setting Comments
0 FLEXIBLE FUNC. Flx OFF
ON
Alarm Only
OFF Flexible Function
0 OPERRAT. MODE Flx 3-phase
1-phase
no reference
3-phase Mode of Operation
0 BLK f out of r Flx YES
NO
YES Block while Freq. is out of
range
0 MEAS. QUANTITY Flx Please select
Current
dV/dt rising
dV/dt falling
Binary Input
Please select Selection of Measured
Quantity
0 MEAS. METHOD Flx Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental Selection of Measure-
ment Method
0 PICKUP WITH Flx Exceeding
Dropping below
Exceeding Pickup with
0 CURRENT Flx Ia
Ib
Ic
In
In sensitive
In2
Ia Current
0 P.U. THRESHOLD Flx 1A 0.03 .. 40.00 A 2.00 A Pickup Threshold
5A 0.15 .. 200.00 A 10.00 A
0 P.U. THRESHOLD Flx 1A 0.03 .. 40.00 A 2.00 A Pickup Threshold
5A 0.15 .. 200.00 A 10.00 A
0 P.U. THRESHOLD Flx 0.001 .. 1.500 A 0.100 A Pickup Threshold
0 P.U. THRESHOLD Flx 2.0 .. 200.0 V 110.0 V Pickup Threshold
0 P.U. THRESHOLD Flx 1A 0.5 .. 10000.0 VAR 200.0 VAR Pickup Threshold
5A 2.5 .. 50000.0 VAR 1000.0 VAR
0 P.U. THRESHOLD Flx 15 .. 100 % 20 % Pickup Threshold
0 P.U. THRESHOLD Flx 4 .. 100 V/s 60 V/s Pickup Threshold
0 T TRIP DELAY Flx 0.00 .. 3600.00 sec 1.00 sec Trip Time Delay
0A T DROPOUT DELAY Flx 0.00 .. 60.00 sec 0.00 sec Dropout Time Delay
0A DROPOUT RATIO Flx 0.70 .. 0.99 0.95 Dropout Ratio
0A DROPOUT RATIO Flx 1.01 .. 3.00 1.05 Dropout Ratio
201 CT Starpoint P.System Data
1
towards Line
towards Busbar
towards Line CT Starpoint
F.2
Functions, Settings, Information
F.2 Settings
386 SIPROTEC 4, 7SJ61, Manual