Jumper Rated Voltage
DC 60 V to 125 V DC 110 V to 250 V,
AC 115 V
DC 24 V/ 48 V AC 230 V
interchangeable cannot be changed
Pickup Voltages of BI1 to BI3
Table 3-3 Jumper settings for the pickup voltages of the binary inputs BI1 to BI3 on the processor board
A–CPU to 7SJ61.../DD
Binary Inputs Jumper
DC 19 V Pickup
1)
DC 88 V Pickup
3)
BI1 X21 L H
BI2 X22 L H
BI3 X23 L H
1)
Factory settings for devices with power supply voltages of DC 24 V to 125 V
2)
Factory settings for devices with power supply voltages of DC 110 V to 220 V and AC 115 V/ 230 V
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7SJ61, Manual 241
C53000-G1140-C210-6, Edition 05.2016