RTS = Request to send
CTS = Clear to send
GND = Signal/Chassis Ground
The cable shield is to be grounded at both ends. For extremely EMC-prone environments, the GND may be
connected via a separate individually shielded wire pair to improve immunity to interference.
Table 3-14 Connector Assignment at the Various Interfaces
Pin-
No.
RS232 RS485 Profibus FMS Slave, RS485 Modbus RS485 EN 100
elektr.
RJ45
IEC 60870–5–103
redundant
RS485 (RJ45)
Profibus DP Slave, RS485 DNP 3.0 RS485
1 Shield (electrically connected with shield shroud) Tx+ B/B’ (RxD/TxD-P)
2 RxD Tx– A/A’ (RxD/TxD-N)
3 TxD A/A’ (RxD/TxD-N) B/B’ (RxD/TxD-P) A Rx+
4 CNTR-A (TTL) RTS (TTL Pegel)
5 GND C/C’ (GND) C/C’ (GND) GND1
6 +5 V (max. load with 100 mA) VCC1 Rx–
7 RTS
1)
8 CTS B/B’ (RxD/TxD-P) A/A’ (RxD/TxD-N) B
9 not
provided
1)
Pin 7 also carries the RTS signal with RS232 level when operated as RS485 interface. Pin 7 must therefore
not be connected!
Termination
The RS485 interface is bus-capable for half-duplex operation with the signals A/A' and B/B' and the common
reference potential C/C' (GND). Verify that only at the bus of the last device the terminating resistors are
connected but not at the bus of the other devices.
The jumpers for the terminating resistors are located on the interface module RS485 (see Figure 3-12) or
Profibus RS485 (see Figure 3-14).
The terminating resistors can also be connected externally (e.g. to the connection module, as illustrated in
Figure 3-16). In this case, the terminating resistors located on the module must be disconnected.
If the bus is extended, make sure again that only the last device on the bus has the terminating resistors
switched-in, and that all other devices on the bus do not.
Time Synchronization Interface
It is optionally possible to process 5 V-, 12 V- or 24 V- time synchronization signals, provided that they are
carried to the inputs named in the following table.
Table 3-15
D-SUB socket assignment of the time synchronization interface
Pin-No. Description Signal Meaning
1 P24_TSIG Input 24 V
2 P5_TSIG Input 5 V
3 M_TSIG Return Line
4
1)
1)
5 SHIELD Shield Potential
6
7 P12_TSIG Input 12 V
8
P_TSYNC
1)
Input 24 V
1)
Mounting and Commissioning
3.2 Checking Connections
SIPROTEC 4, 7SJ61, Manual 261
C53000-G1140-C210-6, Edition 05.2016