EasyManua.ls Logo

Siemens SIPROTEC 4 7SJ61 - Page 308

Siemens SIPROTEC 4 7SJ61
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The dropout time constants apply to (Ι
2
/Ι
2p
) ≤ 0.90
Dropout Value
IEC and ANSI (without Disk Emulation)
approx. 1.05 Ι
2p
, setting value, which is approx. 0.95 · pickup
threshold Ι
2
ANSI with Disk Emulation
approx. 0.90 Ι
2p
setting value
Tolerances
Dropout value Ι
2p
Time for Ι
2
/Ι
2p
≤ 0.90
2 % of setting value or 10 mA for Ι
Nom
= 1 A
or 50 mA für Ι
Nom
= 5 A
5 % of reference (calculated) value +2 % current tolerance,
or 30 ms
Influencing Variables for Pickup Values
Power supply direct voltage in range 0.8
0.8 ≤ V
PS
/V
PSNom
≤ 1.15
1 %
Temperature in range 23.00 °F (-5 °C) ≤ Θ
amb
≤ 131.00 °F (55 °C) 0.5 %/10 K
Frequency in range 25 Hz to 70 Hz 1 %
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
1 %
1 %
Transient overreaction for τ > 100 ms (with full displacement) <5 %
Technical Data
4.8 Negative Sequence Protection (inverse-time characteristics)
308 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016

Table of Contents

Related product manuals