Addr. Parameter Function C Setting Options Default Setting Comments
280 Holmgr. for Σi P.System Data
1
NO
YES
NO Holmgreen-conn. (for fast
sum-i-monit.)
281A Swi.auth.via BI P.System Data
1
NO
YES
OFF
NO Change switch.authority
via binary input
282A Interl.on/offBI P.System Data
1
NO
YES
OFF
NO Interlocking on or off via
binary input
302 CHANGE Change Group Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another
Setting Group
401 WAVEFORM-
TRIGGER
Osc. Fault Rec. Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
402 WAVEFORM DATA Osc. Fault Rec. Fault event
Pow.Sys.Flt.
Fault event Scope of Waveform Data
403 MAX. LENGTH Osc. Fault Rec. 0.30 .. 5.00 sec 2.00 sec Max. length of a Wave-
form Capture Record
404 PRE. TRIG. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior
to Trigger
405 POST REC. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform after
Event
406 BinIn CAPT.TIME Osc. Fault Rec. 0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary
Input
610 FltDisp.LED/LCD Device, General Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
613A 50N/51N/67N w. P.System Data
1
Ignd (measured)
3I0 (calcul.)
Ignd (measured) 50N/51N/67N Ground
Overcurrent with
617A T103 with 16 MV Device, General YES
NO
OFF
NO T103-transfer limeted to
16 meas. values
625A T MIN LED HOLD Device, General 0 .. 60 min; ∞ 0 min Minimum hold time of
latched LEDs
640 Start image DD Device, General image 1
image 2
image 7
image 8
image 9
image 10
image 1 Start image Default
Display
700 GOOSE-Stop Device, General YES
NO
NO GOOSE-Stop
1102 FullScaleCurr. P.System Data
2
10 .. 50000 A 100 A Measurem:FullScaleCur-
rent(Equipm.rating)
1107 I MOTOR START P.System Data
2
1A 0.40 .. 10.00 A 2.50 A Motor Start Current
(Block 49, Start 48)
5A 2.00 .. 50.00 A 12.50 A
Functions, Settings, Information
F.2 Settings
388 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016