Addr. Parameter Function C Setting Options Default Setting Comments
1321A 50N-1 measurem. 50/51 Overcur. Fundamental
True RMS
Fundamental 50N-1 measurement of
1322A 51N measurem. 50/51 Overcur. Fundamental
True RMS
Fundamental 51N measurement of
1330 50N/51N 50/51 Overcur. 1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
50N/51N
1331 MofPU Res T/TEp 50/51 Overcur. 0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
Multiple of Pickup <->
T/TEp
1701 COLDLOAD PICKUP ColdLoadPickup OFF
ON
OFF Cold-Load-Pickup Func-
tion
1702 Start Condition ColdLoadPickup No Current
Breaker Contact
79 ready
No Current Start Condition
1703 CB Open Time ColdLoadPickup 0 .. 21600 sec 3600 sec Circuit Breaker OPEN
Time
1704 Active Time ColdLoadPickup 1 .. 21600 sec 3600 sec Active Time
1705 Stop Time ColdLoadPickup 1 .. 600 sec; ∞ 600 sec Stop Time
1801 50c-2 PICKUP ColdLoadPickup 1A 0.10 .. 35.00 A; ∞ 10.00 A 50c-2 Pickup
5A 0.50 .. 175.00 A; ∞ 50.00 A
1802 50c-2 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.00 sec 50c-2 Time Delay
1803 50c-1 PICKUP ColdLoadPickup 1A 0.10 .. 35.00 A; ∞ 2.00 A 50c-1 Pickup
5A 0.50 .. 175.00 A; ∞ 10.00 A
1804 50c-1 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.30 sec 50c-1 Time Delay
1805 51c PICKUP ColdLoadPickup 1A 0.10 .. 4.00 A 1.50 A 51c Pickup
5A 0.50 .. 20.00 A 7.50 A
1806 51c TIME DIAL ColdLoadPickup 0.05 .. 3.20 sec; ∞ 0.50 sec 51c Time dial
1807 51c TIME DIAL ColdLoadPickup 0.50 .. 15.00 ; ∞ 5.00 51c Time dial
1808 50c-3 PICKUP ColdLoadPickup 1A 1.00 .. 35.00 A; ∞ ∞ A 50c-3 Pickup
5A 5.00 .. 175.00 A; ∞ ∞ A
1809 50c-3 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.00 sec 50c-3 Time Delay
1901 50Nc-2 PICKUP ColdLoadPickup 1A 0.05 .. 35.00 A; ∞ 7.00 A 50Nc-2 Pickup
5A 0.25 .. 175.00 A; ∞ 35.00 A
1902 50Nc-2 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.00 sec 50Nc-2 Time Delay
1903 50Nc-1 PICKUP ColdLoadPickup 1A 0.05 .. 35.00 A; ∞ 1.50 A 50Nc-1 Pickup
5A 0.25 .. 175.00 A; ∞ 7.50 A
1904 50Nc-1 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.30 sec 50Nc-1 Time Delay
1905 51Nc PICKUP ColdLoadPickup 1A 0.05 .. 4.00 A 1.00 A 51Nc Pickup
5A 0.25 .. 20.00 A 5.00 A
1906 51Nc T-DIAL ColdLoadPickup 0.05 .. 3.20 sec; ∞ 0.50 sec 51Nc Time Dial
1907 51Nc T-DIAL ColdLoadPickup 0.50 .. 15.00 ; ∞ 5.00 51Nc Time Dial
1908 50Nc-3 PICKUP ColdLoadPickup 0.25 .. 35.00 A; ∞ ∞ A 50Nc-3 Pickup
1909 50Nc-3 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.00 sec 50Nc-3 Time Delay
2201 INRUSH REST. 50/51 Overcur. OFF
ON
OFF Inrush Restraint
2202 2nd HARMONIC 50/51 Overcur. 10 .. 45 % 15 % 2nd. harmonic in % of
fundamental
2203 CROSS BLOCK 50/51 Overcur. NO
YES
NO Cross Block