Addr. Parameter Function C Setting Options Default Setting Comments
4005 46-2 DELAY 46 Negative
Seq
0.00 .. 60.00 sec; ∞ 1.50 sec 46-2 Time Delay
4006 46 IEC CURVE 46 Negative
Seq
Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv. 46 IEC Curve
4007 46 ANSI CURVE 46 Negative
Seq
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Extremely Inv. 46 ANSI Curve
4008 46-TOC PICKUP 46 Negative
Seq
1A 0.05 .. 2.00 A 0.90 A 46-TOC Pickup
5A 0.25 .. 10.00 A 4.50 A
4009 46-TOC TIMEDIAL 46 Negative
Seq
0.50 .. 15.00 ; ∞ 5.00 46-TOC Time Dial
4010 46-TOC TIMEDIAL 46 Negative
Seq
0.05 .. 3.20 sec; ∞ 0.50 sec 46-TOC Time Dial
4011 46-TOC RESET 46 Negative
Seq
Instantaneous
Disk Emulation
Instantaneous 46-TOC Drop Out
4012A 46 T DROP-OUT 46 Negative
Seq
0.00 .. 60.00 sec 0.00 sec 46 Drop-Out Time Delay
4101 FCT 48 48/66 Motor-
prot
OFF
ON
OFF 48 Startup Time Supervi-
sion for Motors
4102 STARTUP CURRENT 48/66 Motor-
prot
1A 0.50 .. 16.00 A 5.00 A Startup Current
5A 2.50 .. 80.00 A 25.00 A
4103 STARTUP TIME 48/66 Motor-
prot
1.0 .. 180.0 sec 10.0 sec Startup Time
4104 LOCK ROTOR TIME 48/66 Motor-
prot
0.5 .. 180.0 sec; ∞ 2.0 sec Permissible Locked Rotor
Time
4105 STARTUP T WARM 48/66 Motor-
prot
0.5 .. 180.0 sec; ∞ 10.0 sec Startup Time for warm
motor
4106 TEMP.COLD
MOTOR
48/66 Motor-
prot
0 .. 80 %; ∞ 25 % Temperature limit for cold
motor
4201 FCT 49 49 Th.Overload OFF
ON
Alarm Only
OFF 49 Thermal overload
protection
4202 49 K-FACTOR 49 Th.Overload 0.10 .. 4.00 1.10 49 K-Factor
4203 TIME CONSTANT 49 Th.Overload 1.0 .. 999.9 min 100.0 min Time Constant
4204 49 Θ ALARM 49 Th.Overload 50 .. 100 % 90 % 49 Thermal Alarm Stage
4205 I ALARM 49 Th.Overload 1A 0.10 .. 4.00 A 1.00 A Current Overload Alarm
Setpoint
5A 0.50 .. 20.00 A 5.00 A
4207A Kτ-FACTOR 49 Th.Overload 1.0 .. 10.0 1.0 Kt-FACTOR when motor
stops
4208A T EMERGENCY 49 Th.Overload 10 .. 15000 sec 100 sec Emergency time
4209 49 TEMP. RISE I 49 Th.Overload 40 .. 200 °C 100 °C 49 Temperature rise at
rated sec. curr.
4210 49 TEMP. RISE I 49 Th.Overload 104 .. 392 °F 212 °F 49 Temperature rise at
rated sec. curr.
4211 TEMPSENSOR RTD 49 Th.Overload 1 .. 6 1 Temperature sensor
connected to RTD
4212 TEMPSENSOR RTD 49 Th.Overload 1 .. 12 1 Temperature sensor
connected to RTD
Functions, Settings, Information
F.2 Settings
394 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016