Addr. Parameter Function C Setting Options Default Setting Comments
7101 FCT 79 79M Auto Recl. OFF
ON
OFF 79 Auto-Reclose Function
7103 BLOCK MC Dur. 79M Auto Recl. 0.50 .. 320.00 sec;
0
1.00 sec AR blocking duration after
manual close
7105 TIME RESTRAINT 79M Auto Recl. 0.50 .. 320.00 sec 3.00 sec 79 Auto Reclosing reset
time
7108 SAFETY 79 ready 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Safety Time until 79 is
ready
7113 CHECK CB? 79M Auto Recl. No check
Chk each cycle
No check Check circuit breaker
before AR?
7114 T-Start MONITOR 79M Auto Recl. 0.01 .. 320.00 sec;
∞
0.50 sec AR start-signal monitoring
time
7115 CB TIME OUT 79M Auto Recl. 0.10 .. 320.00 sec 3.00 sec Circuit Breaker (CB)
Supervision Time
7116 Max. DEAD EXT. 79M Auto Recl. 0.50 .. 1800.00 sec;
∞
100.00 sec Maximum dead time
extension
7117 T-ACTION 79M Auto Recl. 0.01 .. 320.00 sec;
∞
∞ sec Action time
7118 T DEAD DELAY 79M Auto Recl. 0.0 .. 1800.0 sec; ∞ 1.0 sec Maximum Time Delay of
Dead-Time Start
7127 DEADTIME 1: PH 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Dead Time 1: Phase Fault
7128 DEADTIME 1: G 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Dead Time 1: Ground
Fault
7129 DEADTIME 2: PH 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Dead Time 2: Phase Fault
7130 DEADTIME 2: G 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Dead Time 2: Ground
Fault
7131 DEADTIME 3: PH 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Dead Time 3: Phase Fault
7132 DEADTIME 3: G 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Dead Time 3: Ground
Fault
7133 DEADTIME 4: PH 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Dead Time 4: Phase Fault
7134 DEADTIME 4: G 79M Auto Recl. 0.01 .. 320.00 sec 0.50 sec Dead Time 4: Ground
Fault
7135 # OF RECL. GND 79M Auto Recl. 0 .. 9 1 Number of Reclosing
Cycles Ground
7136 # OF RECL. PH 79M Auto Recl. 0 .. 9 1 Number of Reclosing
Cycles Phase
7137 Cmd.via control 79M Auto Recl. (Einstellmöglich-
keiten anwendung-
sabhängig)
none Close command via
control device
7139 External SYNC 79M Auto Recl. YES
NO
NO External 25 synchronisa-
tion
7140 ZONE SEQ.COORD. 79M Auto Recl. OFF
ON
OFF ZSC - Zone sequence
coordination
7150 50-1 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50-1
7151 50N-1 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50N-1
Functions, Settings, Information
F.2 Settings
396 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016