Addr. Parameter Function C Setting Options Default Setting Comments
9082A RTD 8 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 8: Location
9083 RTD 8 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 8: Temperature Stage
1 Pickup
9084 RTD 8 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 8: Temperature Stage
1 Pickup
9085 RTD 8 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 8: Temperature Stage
2 Pickup
9086 RTD 8 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 8: Temperature Stage
2 Pickup
9091A RTD 9 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 9: Type
9092A RTD 9 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 9: Location
9093 RTD 9 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 9: Temperature Stage
1 Pickup
9094 RTD 9 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 9: Temperature Stage
1 Pickup
9095 RTD 9 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 9: Temperature Stage
2 Pickup
9096 RTD 9 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 9: Temperature Stage
2 Pickup
9101A RTD10 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD10: Type
9102A RTD10 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD10: Location
9103 RTD10 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD10: Temperature
Stage 1 Pickup
9104 RTD10 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD10: Temperature
Stage 1 Pickup
9105 RTD10 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD10: Temperature
Stage 2 Pickup
9106 RTD10 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD10: Temperature
Stage 2 Pickup