No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
916 Increment of active
energy (WpΔ=)
Energy -
917 Increment of reactive
energy (WqΔ=)
Energy -
1020 Counter of operating
hours (Op.Hours=)
Statistics VI
1021 Accumulation of inter-
rupted current Ph A (Σ Ia
=)
Statistics VI
1022 Accumulation of inter-
rupted current Ph B (Σ Ib
=)
Statistics VI
1023 Accumulation of inter-
rupted current Ph C (Σ Ic
=)
Statistics VI
1202 >BLOCK 50Ns-2 (>BLOCK
50Ns-2)
Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
2
1 Yes
1203 >BLOCK 50Ns-1 (>BLOCK
50Ns-1)
Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
3
1 Yes
1204 >BLOCK 51Ns (>BLOCK
51Ns)
Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
4
1 Yes
1207 >BLOCK 50Ns/67Ns (>BLK
50Ns/67Ns)
Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
7
1 Yes
1211 50Ns/67Ns is OFF (50Ns/
67Ns OFF)
Sens. Gnd
Fault
OUT On
Of
f
* * LED BO 15
1
11
1
1 Yes
1212 50Ns/67Ns is ACTIVE
(50Ns/67Ns ACT)
Sens. Gnd
Fault
OUT On
Of
f
* * LED BO 15
1
11
2
1 Yes
1221 50Ns-2 Pickup (50Ns-2
Pickup)
Sens. Gnd
Fault
OUT * On
Off
On
Off
* LED BO 15
1
12
1
2 Yes
1223 50Ns-2 TRIP (50Ns-2 TRIP) Sens. Gnd
Fault
OUT * On On
Off
m LED BO 15
1
12
3
2 Yes
1224 50Ns-1 Pickup (50Ns-1
Pickup)
Sens. Gnd
Fault
OUT * On
Off
On
Off
* LED BO 15
1
12
4
2 Yes
1226 50Ns-1 TRIP (50Ns-1 TRIP) Sens. Gnd
Fault
OUT * On On
Off
m LED BO 15
1
12
6
2 Yes
1227 51Ns picked up (51Ns
Pickup)
Sens. Gnd
Fault
OUT * On
Off
* LED BO 15
1
12
7
2 Yes
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ61, Manual 417
C53000-G1140-C210-6, Edition 05.2016