No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
2785 79 - Auto-reclose is
dynamically BLOCKED (79
DynBlock)
79M Auto
Recl.
OUT On
Of
f
On * LED BO 40 85 1 Yes
2788 79: CB ready monitoring
window expired (79 T-
CBreadyExp)
79M Auto
Recl.
OUT On * * LED BO
2801 79 - in progress (79 in
progress)
79M Auto
Recl.
OUT * On * LED BO 40 10
1
2 Yes
2808 79: CB open with no trip
(79 BLK: CB open)
79M Auto
Recl.
OUT On
Of
f
* * LED BO
2809 79: Start-signal moni-
toring time expired (79 T-
Start Exp)
79M Auto
Recl.
OUT On * * LED BO
2810 79: Maximum dead time
expired (79 TdeadMax
Exp)
79M Auto
Recl.
OUT On * * LED BO
2823 79: no starter configured
(79 no starter)
79M Auto
Recl.
OUT On
Of
f
* * LED BO
2824 79: no cycle configured
(79 no cycle)
79M Auto
Recl.
OUT On
Of
f
* * LED BO
2827 79: blocking due to trip
(79 BLK by trip)
79M Auto
Recl.
OUT On * * LED BO
2828 79: blocking due to 3-
phase pickup (79 BLK:3ph
p.u.)
79M Auto
Recl.
OUT On * * LED BO
2829 79: action time expired
before trip (79 Tact
expired)
79M Auto
Recl.
OUT On * * LED BO
2830 79: max. no. of cycles
exceeded (79 Max. No.
Cyc)
79M Auto
Recl.
OUT On * * LED BO
2844 79 1st cycle running (79
1stCyc. run.)
79M Auto
Recl.
OUT * On * LED BO
2845 79 2nd cycle running (79
2ndCyc. run.)
79M Auto
Recl.
OUT * On * LED BO
2846 79 3rd cycle running (79
3rdCyc. run.)
79M Auto
Recl.
OUT * On * LED BO
2847 79 4th or higher cycle
running (79 4thCyc. run.)
79M Auto
Recl.
OUT * On * LED BO
2851 79 - Close command (79
Close)
79M Auto
Recl.
OUT * On m LED BO 16
0
12
8
2 No
Functions, Settings, Information
F.3 Information List
424 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016