EasyManua.ls Logo

Siemens SIPROTEC 4 7SJ61 - Page 432

Siemens SIPROTEC 4 7SJ61
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
14111 Fail: RTD 1 (broken wire/
shorted) (Fail: RTD 1)
RTD-Box OUT On
Of
f
* * LED BO
14112 RTD 1 Temperature stage
1 picked up (RTD 1 St.1
p.up)
RTD-Box OUT On
Of
f
* * LED BO
14113 RTD 1 Temperature stage
2 picked up (RTD 1 St.2
p.up)
RTD-Box OUT On
Of
f
* * LED BO
14121 Fail: RTD 2 (broken wire/
shorted) (Fail: RTD 2)
RTD-Box OUT On
Of
f
* * LED BO
14122 RTD 2 Temperature stage
1 picked up (RTD 2 St.1
p.up)
RTD-Box OUT On
Of
f
* * LED BO
14123 RTD 2 Temperature stage
2 picked up (RTD 2 St.2
p.up)
RTD-Box OUT On
Of
f
* * LED BO
14131 Fail: RTD 3 (broken wire/
shorted) (Fail: RTD 3)
RTD-Box OUT On
Of
f
* * LED BO
14132 RTD 3 Temperature stage
1 picked up (RTD 3 St.1
p.up)
RTD-Box OUT On
Of
f
* * LED BO
14133 RTD 3 Temperature stage
2 picked up (RTD 3 St.2
p.up)
RTD-Box OUT On
Of
f
* * LED BO
14141 Fail: RTD 4 (broken wire/
shorted) (Fail: RTD 4)
RTD-Box OUT On
Of
f
* * LED BO
14142 RTD 4 Temperature stage
1 picked up (RTD 4 St.1
p.up)
RTD-Box OUT On
Of
f
* * LED BO
14143 RTD 4 Temperature stage
2 picked up (RTD 4 St.2
p.up)
RTD-Box OUT On
Of
f
* * LED BO
14151 Fail: RTD 5 (broken wire/
shorted) (Fail: RTD 5)
RTD-Box OUT On
Of
f
* * LED BO
14152 RTD 5 Temperature stage
1 picked up (RTD 5 St.1
p.up)
RTD-Box OUT On
Of
f
* * LED BO
Functions, Settings, Information
F.3 Information List
432 SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016

Table of Contents

Related product manuals