Troubleshooting
SITOP UPS1600 / BAT1600 / UPS1100
182 Equipment Manual, 07.2021, A5E37775406-11-76
Error
Type
Ex-
tend-
ed
Error
Severity Alarm Text Help Text
An attempt was made to update the software with an update
file that is not suitable for the UPS1600.
Error during software update - try to update the software again
An attempt was made to update the software with an invalid
update file. The update file is probably too old.
An entry in the software update cannot contain more than
32 bytes of reference data.
Buffer mode is not possible
Buffer mode not possible - check cabling, fuse and battery
voltages
Device temperature critical
(too high)
Device temperature higher than 100 °C. Caution: The highest
permitted temperature could be exceeded!
Device temperature critical
(too low)
Device temperature less than -10 °C. Device could leave the
operating range.
High-resistance connection
to battery
High-resistance connection to battery - check battery power
cable
Power supply to at least one
battery interrupted
Connection to battery interrupted - check connection and fuse
Data from the battery cannot be read correctly. Battery is defec-
tive or not supported by SIEMENS.
Output current of UPS1600 is too high. Output is switched off
for 20 s. The output is switched on again after 20 s.
UPS1600 off - buffer time exceeded.
The UPS1600 output was shut down as result of executing an
instruction or an error situation (e.g. overtemperature, exces-
Output switched on
obsolete from V2.3
The UPS1600 output was switched on again as result of execut-
ing an instruction or the correction of an error situation.
Input voltage at UPS1600 was OK again before the buffer time
expired. Connected devices are reset by switching off the
UPS1600 outputs for the configured time.
A cyclic battery test will be performed
Remark:
For firmware versions from V2.2 - and for versions V2.0.× from
version V2.0.5, the alarm is deactivated.
Software update successful
Previous software update was successful - UPS1600 is opera-
tional again.
Input voltage is too high
Input voltage exceeds 30 V. UPS1600 is not operational.
More than 6 batteries are connected. Connect max. of
6 batteries to the Energy Storage Link.
UPS1600 parameters cor-
rupt
UPS1600-parameters corrupt - try to update the software.
Output and battery charging is switched off to prevent damage
to the device.
Capacity test being performed