Troubleshooting
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
183
Error
Type
Ex-
tend-
ed
Error
Severity Alarm Text Help Text
Input voltage of UPS1600 is too low. UPS1600 is not ready for
buffering.
Device is in buffer mode.
Communication with device
failed
PROFINET connection available - UPS1600 is defective
Wrong battery polarity - check battery connections.
Insufficient charge level
The battery charge level is too low to guarantee the configured
buffer capacity.
Battery is deep discharged - no buffering possible
Buffer readiness disabled
Buffer mode was deactivated by the bridge, rotary coding
switch or in REMOTE mode per command.
Shutdown completed, ping
test successfully completed.
UPS1600 was successfully shut down.
Charge current reduced due
to system load
Charge current was reduced due to system load
Battery is fully charged, buffer standby available
Charging current reduced
manually
The charging current has been reduced by manual adjustment.
The charging function was
deactivated by a control
The charging function was deactivated by a control command
The batteries are no longer charged.
Battery almost discharged as
the charging function is
The battery is almost discharged as the charging function is
deactivated. It is recommended that the charging function is
Battery parameters corrupt
(battery index: 1)
Battery defective - replace battery
Battery parameters corrupt
(battery index: 2)
Battery defective - replace battery
Battery parameters corrupt
(battery index: 3)
Battery defective - replace battery
Battery parameters corrupt
(battery index: 4)
Battery defective - replace battery
Battery parameters corrupt
(battery index: 5)
Battery defective - replace battery
Battery parameters corrupt
(battery index: 6)
Battery defective - replace battery
Battery defective (battery
index: {1:d})
Battery defective - check fuse and battery voltages.
Deep discharge battery, no
charging possible (battery
Battery is deep discharged - replace battery.
Battery temperature high
(battery index: {1:d})
Battery temperature too high - battery life will be shortened
Battery temperature low
(battery index: {1:d}).
Battery temperature too low - reduced buffer current
Communication with battery
fault (battery index: {1:d})
Communication with formerly known battery is no longer pos-
sible - check communication