ID Icons Message Cause/Action
206 CH3 pulse overflow Pulse output has insufficient pulse separation. Increase
Amount per pulse, or reduce Pulse width, or reduce Pulses
per amount.
207 CH4 loop current in lower
saturation
The process value is so low that the loop current reaches
the lower saturation limit and cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
208 CH4 loop current in upper
saturation
The process value is so high that the loop current reaches
the upper saturation limit and cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
209 CH4 cable break Check current output cable connection. Passive operation:
check external power supply.
210 CH4 output frequency too
low
The process value is below the parameter 'Lower range
value'. The output frequency cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
211 CH4 output frequency too
high
The process value is above the parameter 'Upper range
value'. The output frequency cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
212 CH3 pulse overflow Pulse output has insufficient pulse separation. Increase
Amount per pulse, or reduce Pulse width, or reduce Pulses
per amount.
213 Invalid dosing settings Correct settings.
214 CH2 simulated Disable the simulation to return to normal operation.
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB 187