Parameter Default val‐
ue
Value
range
Access
level
Description
411 Totalizer 2 change date Last change
date
dd-mm-
yyyy;
hh:mm:ss
Read Date and time when totalizer 2 function was
changed
Pipe data
300 Number of paths Product de‐
pendent
2 R/W Number of paths on the sensor
302 Max sample frequency 15 15 Read The maximum frequency for flow measure‐
ment
303 Sample frequency 0.5 15 HW key The frequency at which the flow is measured
304 Rn for path 1 Product de‐
pendent
3.4E+38 m Read R-factor for path 1.
For FUS080/SONOKIT (retrofit) installations
this parameter will automatically be calcula‐
ted by the pipe geometric tool (see "Pipe geo.
assistant" in "Device" menu).
305 Rn for path 2 Product de‐
pendent
3.4E+38 m Read R-factor for path 2.
For FUS080/SONOKIT (retrofit) installations
this parameter will automatically be calcula‐
ted by the pipe geometric tool (see "Pipe geo.
assistant" in "Device" menu).
Valid only for 2-path solutions
306 Inner pipe diameter Product de‐
pendent
0.050 to
1.200 m
Read Inner pipe diameter in meters.
For FUS080/SONOKIT (retrofit) installations
this parameter will automatically be calcula‐
ted by the pipe geometric tool (see "Pipe geo.
assistant" in "Device" menu).
Parameter lists
A.4 Meter setup
SITRANS FUS380/FUE380
Operating Instructions, 05/2018, A5E00730100-AE 107