6.5.7 Output B, terminals 66/67:
The output B setting must be selected according to application specific requirements (default
setting = Alarm).
Preset to alarm indication:
$ODUPRXWSXW
$ODUPVWDWXV
2Q
2II
(UURU
1R(UURU
Example: If track 1 is not measuring, a appears on display. Failure code F1 appears in
display menu 4, and relay output terminals switch to Off.
Call up indication:
&DOOXSRXWSXW
2Q
2II
2Q
2II
&DOOXSUHVHW
&DOOXSVWDWXV
When output B is configured as Call-up, the output is activated by an alarm condition and
remains on until it is manually reset via communication interface and the PDM program (or via
manually power down of the device).
A new alarm will not activate a Call-up function if the Call-up function is still active from a
previous alarm.
6.5.8 Optional current output, terminals 31/32
1. In SIMATIC PDM navigate to [OutputOption module] in the structure tree.
2. Set
Selection of option module
to Current output.
3. Make sure that
Enable
is set to Yes.
Figure 6-3 PDM Example
Commissioning
6.5 Commissioning via PDM
SITRANS FUS380/FUE380
Operating Instructions, 05/2018, A5E00730100-AE 61