4. Set required parameters.
5. Click on [Download to device] icon to apply settings.
See also parameters listed in Output (Page 98).
Note
Default settings
The 4 mA always equals 0 flow rate and the 20 mA (parameter 907) equals the Qp value
selected via the order code. The default Qp can be found on the transmitter nameplate.
Note
IrDA communication
The IrDA communication has higher priority than the communication on the output signals.
During IrDA communication with the transmitter, the transmitter will keep measuring, but the
signal from the current output module will show the last value received from the transmitter for
up to 40 seconds. After that the signal will show the selected error signal (default 3.6 mA) even
if
Alarm
[912] is set to Off.
Note
Alarm signal
The alarm signal has higher priority than the
Fixed flow mode enable
(510) and
Fixed flow value
(511). To use this fixed flow (for example during a test where an alarm signal may appear) the
alarm signal for current output module (912) must be disabled (set to [Off]).
Note
Power off
The settings for
Fixed mode
(910) and
Fixed value
(911) will not be reset
at power off.
Note
Start-up
During system start-up the current output signal is 3.6 mA (4 mA if the output function setting
is disabled).
Commissioning
6.5 Commissioning via PDM
SITRANS FUS380/FUE380
62 Operating Instructions, 05/2018, A5E00730100-AE