Parameter Default value Value range Access
level
Description
9 Flow unit m
3
/h See Table A-7
Flow rate units
(Page 109)
R/W Flow unit as text for actual flowrate. Change
the unit in parameter table if the device
menu "Unit guide (offline)" does not list the
wanted unit.
Note: The device display can show "m
3
/s"
unit only - other units cannot be shown on
the display, but will be used and shown on‐
line via PDM.
10 Maximum flow Qmax 1000000 m
3
/h R/W Maximum flow
20 Vendor name Siemens AG Read Siemens AG Flow Instruments, Germany
21 Module type Product de‐
pendent
FUE380
FUS380
Read Type of flowmeter, depending on ordered
system
22 Software version 2.03 Read Software version of the flowmeter
23 Product code number Product de‐
pendent
Read Siemens production sales code number
(the first part of the system number on the
nameplate)
24 System Serial number Product de‐
pendent
R/W Siemens production number (the s econd
part of the system number on the nameplate
25 Transmitter serial num‐
ber
Product de‐
pendent
HW key Serial number of the electronics
26 Sensor serial number Product de‐
pendent
Read Serial number of the sensor
A.2 Output
Table A-2 Output parameters
Parameter Default val‐
ue
Value range Access
level
Description
100 Actual date and time Product de‐
pendent
R/W Actual date and time (day-month-year
and hours:minutes:seconds)
101 Totalizer 1 0 -2000000001 to
+2000000001
Read Volume for totalization register 1
102 Totalizer 2 0 -2000000001 to
+2000000001
Read Volume for totalization register 2
103 Customer totalizer 3 0 Read Customer totalizer 3 based on totalizer 1
set up
104 Reset customer totalizer 3 No No, Yes R/W Reset of customer totalizer
105 Customer totalizer 3 reset date Last reset
date
dd-mm-yyyy,
hh:mm:ss
Read Date and time when customer totalizer
has been reset
106 Flow rate Read Actual flow value
107 Relative flow 0 Read Actual flow value in relation to Qmax
108 Actual flow velocity for path 1 0 Read The actual flow velocity for path 1 in m/s
(SI-unit)