Siemens SITRANS FUS380 - Adding the Device to the Network

Siemens SITRANS FUS380
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.5.3 Adding the device to the network
It is recommended to configure the FUS080 project in PDM before setting the parameters.
Add device to SIMATIC Modbus network:
1. Select [FileNew]
Type in a project name.
2. Right click on your new project, select [Insert New ObjectNetworks].
3. Right click on your Networks, select [Insert New ObjectCommunication Network].
4. Click on [Assign Device Type] and select NetworksMODBUS → MODBUS networks
MODBUS network.
5. Click [OK] and click [OK] again.
6. Right click on MODBUS network and select [Insert New ObjectObject]
7. Click on [Assign Device Type] and assign the MODBUS device to SITRANS FUS/E080
[DevicesMODBUSSensorsFlowUltrasonicSIEMENS AGSITRANS FUS/
E080] and click [OK].
Name device according to application requirements (max. 32 characters) and click [OK].
Set up communication parameters for SIMATIC MODBUS network.
8. Select NetworksMODBUS network.
9. Right click on Modbus network and select Object Properties.
10.On the Communication tab, select MODBUS communication to activate IrDA.
Commissioning
6.5 Commissioning via PDM
SITRANS FUS380/FUE380
56 Operating Instructions, 05/2018, A5E00730100-AE