Parameter Factory settings Possible settings
Flow unit factor 3600 (for flow unit m
3
/h) Auto set from unit guide
Totalizer volume unit factor 1 Auto set from unit guide
Flow unit text m
3
/h Auto set from unit guide, but only m
3
/h
can be shown on display
Totalizer unit text m
3
Auto set from unit guide, but only m
3
can
be shown on display
Totalizer directions
Totalizer 1 direction Forward Forward/Reverse/Forward net/Reverse
net
Totalizer 2 direction Reverse Forward/Reverse/Forward net/Reverse
net
Output A
Active On On/off
Direction Factory pre-configured according order
code.
Preset: Forward
Forward/Reverse/Forward net/Reverse
net
Amount per pulse Factory pre-configured according order
code, i.e. 0.1 m
3
Unit: The same as Totalizer unit
Value freely selectable
Pulse width Factory pre-configured according order
code. Typically 5 ms
5, 10, 20, 50, 100, 200, 500 ms
Output B
Active On On/Off
Function Alarm Pulse/Alarm/Call up
Direction No influence, while "Alarm" Forward/Reverse/Forward net/Reverse
net
Amount per pulse No influence, while "Alarm" Unit: The same as Totalizer unit
Value freely selectable
Pulse width No influence, while "Alarm" 5, 10, 20, 50, 100, 200, 500 ms
Current output (optional add-on module)
Enable Yes Yes/No
Scaling 4 mA: always equals 0 flow rate
20 mA: equals the Qp value (product
dependent)
Low flow cut-off (parameter 373) to
Qmax (parameter 10)
Direction Forward Forward, Reverse, Bidirectional
Fixed mode No Yes/No
Fixed value 4 mA 3 to 24 mA
Alarm level 3.6 mA 3.6 mA, 22.5 mA, Off
B.2 Factory settings for Modbus communication
Parameter Default setting
Slave device address 1
Data transmission rate 19 200 baud
Settings
B.2 Factory settings for Modbus communication
SITRANS FUS380/FUE380
112 Operating Instructions, 05/2018, A5E00730100-AE