3.1 Application limitations
–
no monitored remote control panel
–
not usable for multi-sector installations with electrical cylinder allocation and full
redundancy
–
no provision to monitor a spare cylinder bank
–
no facility for secondary flooding control (low pressure installations)
–
no interface for VdS peripherals such as FBF, ÜE, FSD, SST
3.2 Specified standards and options
EN12094-1
Fulfilled
Basic functions
x
Options and the associated requirements Related XC10 configuration
4.17
Delay of extinguishing signal
Monitored control line 4, programming step 1 option 1-13 x
4.18
Signal representing the flow of extinguishing
agent
Monitored input 1, programming step 4 option 1
Monitored input 1A (XCA1016) programming step 4 option 1
x
Monitoring of the status of components
Loss of agent
Monitored input 2, programming step 4 option 10
Monitored input 1B (XCA1016) programming step 4 option 1
4.19
Non-electrical blocking device
Monitored input 2, programming step 4 option 6
x
4.20
Emergency hold
Monitored input 3, programming step 8 option 2 x
4.21
Control of flooding time
-
4.22
Initiation of secondary flooding
-
4.23
Manual only mode
Key "Mode select"
Monitored input 3, programming step 8 option 6
x
4.24
Triggering signals to equipment within the
system
Monitored control line 3, programming step 5 option 15-25 x
4.25
Extinguishing signals to spare cylinders
-
4.26
Triggering of equipment outside the system
Driver output 1 and 2
Monitored control line 5, programming step 1 option 17
x
4.27
Emergency abort
Monitored input 3, programming step 8 option 1 x
4.28
Control of extended discharge
-
4.29
Release of the extinguishing media for selected
flooding
-
4.30
Activation of alarm devices with different signals
Monitored control line 1, programming step 5 option 1-10 x
EN54-2
Fulfilled
Basic functions
x
Options and associated requirements Related XC10 configuration
7.8
Output to fire alarm device in accordance with
EN54-1 / C
Monitored control line 1, programming step 5 option 1-10 x
7.9
Output to fire alarm routing equipment in
accordance with EN54-1 / E
Monitored control line 2, programming step 3 option 17 x
7.10
Output to fire protection equipment or in
accordance with EN54-1 / G
Monitored control line 2, programming step 3 option 18 or 19 x
7.11
Delay to outputs
-
7.12
Coincidence detection
Detector zones 1, 2 and 3, programming step 6 option 1-4 x
7.13
Alarm counter
-
8.3
Fault signals from points
x
8.4
Total loss of the power supply
Separate wire from battery to upper main board XCM1001-2 x
8.9
Output to fault warning routing equipment in
accordance with EN54-1 / J
Potential-free contact Nr. 2, programming step 3 option 8-11 x
10
Test condition
x