5.3 Adjusting elements
Certain functions can be parameterized using the adjusting elements.
5.3.1 Adjusting elements of the XCM1001-1 lower main board
This board contains parameters for:
–
Disable earth fault monitoring
–
Change type of fire detector
Fig. 11 Adjusting elements of the XCM1001-2 upper main board
Ref. Function State Parameter
ON Activated (factory setting) PU1 Earth short
monitoring unit
OFF De-activated
ON Detector "Siemens" without current limiting (factory setting) SW1-1 Detector line 1
OFF Detector "Synova" with current limiting
ON Detector "Siemens" without current limiting (factory setting) SW1-2 Detector line 2
OFF Detector "Synova" with current limiting
ON Detector "Siemens" without current limiting (factory setting) SW2-3 Detector line 3
OFF Detector "Synova" with current limiting
ON
1
) Detector "Siemens" without current limiting (factory setting) SW2-4 Detector line 4
(manual release)
OFF
1
) Detector "Synova" with current limiting
Fit Fuse “F1” for control line 4 F1 / F2 Pluggable fuse 2A
Fit Fuse “F2” for control line 5
1
) Manual activation buttons with 820 Ohm resistor or with Z-diode 5.6 V with LED in line function on
both settings correct