Programming the user functions
88
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.14 Step 14, change the fault delay upon "Mains failure"
Change the fault delay upon "Mains failure"
Zone 1 Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
1 Delay = 0 sec
2 Delay = 3 minutes
3 (default)
Delay = 10 minutes
4 Delay = 30 minutes
KEY13
5 Delay = 3 hours
11.6.15 Step 15, change the function of the control inputs 2 to 4
Change the function of control input 2
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
1 (default)
Initiate function "Silence buzzer"
2
)
2 Enable state "Manual only"
1
)
3 Enable state "Autom. & Man. blocked"
1
)
4 Enable state "External device disabled"
1
)
5 Enable "RT-alarm" + "RT-fault" disabled
1
)
6 Enable state "Emergency hold"
1
)
KEY13
7 Enable "Control line 1" + "Fire alarm" (LED6)
1
)
Change the function of control input 3
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
8 (default)
Enable state "Fault"
1
)
9 Enable state "External power supply fault"
1
)
10 Enable state "RT-fault"
1
)
11 Enable state "Access level 2 enabled"
1
)
12 Enable state "Emergency abort"
1
)
13 Initiate function "Silence buzzer"
2
)
KEY14
14 Enable state "Manual only"
1
)
Change the function of control input 4
Zone 1 Zone 2
Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
15 (default)
Release "Silence Re-sound Horn" function
2
)
16 Enable state "No fault" (inverse)
3
)
17 Enable state "RT-fault"
1
)
18 Enable state "Access level 2 enabled"
1
)
19 Enable state "Emergency abort"
1
)
20 Initiate function "Silence buzzer"
2
)
KEY15
21 Enable "Control line 1" & LED6 "Fire alarm"
1
)
1
) The state lasts as long as a positive potential is applied to the input
2
) The functions must be triggered by a pulse
3
) As soon as the positive potential is no longer on the input, a fault is
triggered