Programming the user functions
86
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.12 Step 12, change the code for access level 2
Change the basic code for access level 2
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
1 (default)
Access code "4233" defined – –
2
Individual access code:
1. Enter the access code by pressing the keys 4 to 7 (digits 1 to 4) in
the desired sequence (max. 4 digits)
2. Press KEY13 (zone 1)
–
LED27 (zone 1, red) flashes
3. Repeat steps 1 and 2 (confirm access code)
–
LED27 (zone 1, red) lit continuously (access code accepted)
–
LED28 (zone 1, yellow) flashes (code not accepted; repeat steps
1 to 3)
–
KEY13
▼
3
No access code required (access level 2 is released via key switch)
Press key13 & 14 simultaneously after procedure described in option
2 have been done
Change the access level for the function "Silence buzzer"
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
4 (default)
Can always be silenced –
KEY14
▼
5 Possible only on access level 2