Programming the user functions
80
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.5 Step 5, change the active mode of control lines 1 and 3
Change the active mode of control line 1
Zone 1 Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
1 (default)
State "Fire alarm" = continuous
2 State "Fire alarm" = pulsating slow (1sec active/4sec inactive)
3 State "Fire alarm" = not activated
4 State "Fire alarm" = pulsating fast (1sec active/1sec inactive)
5 (default)
State "Activated" = pulsating fast and pulsating slow in state
"Emergency hold/abort"
6 State "Activated" = continuous
7
State "Activated" = continuous and pulsating slow in state
"Emergency hold"
KEY13
8
State "Activated" = pulsating long (4sec active/1sec inactive) and
pulsating fast in state "Emergency hold/abort"
9 (default)
State "Released" = pulsating fast
KEY14
10 State "Released" = continuous
Change the active period of control line 1
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
11 (default)
Active until "Silence Re-sound horn" and "Reset"
12 Active until "Reset"
13
Active until "Silence Re-sound horn" and "Reset" but only after timer
of 5 min has elapsed
KEY14
14
Active until "Silence Re-sound horn" and "Reset" but only after timer
of 30 min has elapsed
Change the active mode and active period of control line 3
Zone 1 Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
15 (default)
State "Fire alarm" = not activated
16 State "Fire alarm" = continuous
17 State "Fire alarm" = pulsating fast
18 (default)
State "Activated" = continuous
KEY15
19 State "Activated" = pulsating fast
20 (default)
State "Released" = continuous until "Reset"
21
State "Released" = continuous until "Silence Re-sound horn" or
"Reset"
22
State "Released" = continuous until "Digit key 4" is pressed after
"Reset"
23 State "Released" = pulsating fast until "Reset"
24
State "Released" = pulsating fast until "Silence Re-sound horn" or
"Reset"
KEY16
25
State "Released" = pulsating fast until "Digit key 4" is pressed after
"Reset"