System overview
11
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
3 System overview
The XC1003-A extinguishing control unit with extinguishing control system and
extinguishing operation and its own fire detection system operates independently
or in conjunction with a fire alarm system. The control unit monitors and controls an
area of a small to medium-size high pressure extinguishing system. It monitors the
area to be flooded, the adjacent areas, the extinguishing process, the control of the
optical and acoustic alarm and the stocks of extinguishing agent.
Fig. 1 XC1003-A Extinguishing control unit system overview
Use
The XC1003-A control unit can be used for:
Gas extinguishing installations using common extinguishing agents such as
CO
2
, FM200, NOVEC and Argon.
Deluge installations using water as the extinguishing agent.
Foam extinguishing installations using a mixture of water and foaming
substances.
Peripheral equipment
The following peripheral equipment can be connected to the XC1003-A control
unit.
Two detector lines with conventional detectors for automatic activation of
extinguishing (zones 1 and 2).
One detector line with conventional detectors for monitoring areas adjacent to
the extinguishing zone (zone 3).
Manual activation button(s) for manual activation of extinguishing (zone 4).
Emergency hold or abort button(s) for manual blocking of extinguishing.
Alarm horn(s) for acoustic reporting of a fire alarm and the activated condition.
Illuminated warning panel(s) for optical reporting of the impending extinguishing
operation during the activated condition time and the released condition.
Remote transmission device to report the "Fire alarm" and "Fault" conditions.
Relay for fire control with 230V contact.
Potential-free contacts to report the states of the XC1003-A control unit
Solenoid or pyrotechnical actuators to trigger the flooding.
Repeater indication panel for extinguishing areas with several entrances.