Programming the user functions
85
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.10 Step 10, change the indication mode on the operator interface
Change the indication of the blocking states
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
1 (default)
Indication mode "Standard":
–
LED 3 = not used
–
LED 4 = "Manual only"
–
LED 5 = "Autom. & Man. blocked"
–
KEY13
▼
2 Indication mode "Alternative":
–
LED 3 = "Manual only"
–
LED 4 = "Autom. & Man." (normal)
–
LED 5 = "Autom. & Man. blocked"
Change the active mode of indicator "Released" (LED8)
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
3 (default)
Flashing when activated –
KEY14
▼
4 Always in steady mode when activated
11.6.11 Step 11, change the function of the detector zones 1 to 3
Change the function of the detector zones 1 and 2
Zone 1 Zone 2
Zone 3 Zone 4
Select Option Function
Red
1 (default)
"Alarm" zone 1 and zone 2 = "Activated"
"Alarm" zone 1 or zone 2 = "Fire alarm"
– – – –
2
"Alarm" zone 1 = "Fire alarm"
"Alarm" zone 2 = "Activated"
– – –
3
Same as option 2 but functions "Enable/Disable Zones" and
"Enable/Disable Detector test" suppressed
–
– –
4
"Alarm" zone 1 or zone 2 = "Activated"
– –
–
KEY13
▼
5 Zone 1 and zone 2 not used – – –
Change the line fault processing of the detector zones 1 and 2
Zone 1 Zone 2
Zone 3
Zone 4
Select Option Function
Red
6 (default)
Line open and line short circuit = "Fault" – –
7 Line open = "Alarm"
–
KEY14
▼
8 Line short circuit = "Alarm" –
Change the function of the detector zone 3
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
9 (default)
"Alarm" zone 3 = Activate fire control lines, RT-alarm (if option 3 or 4
programmed in step 3), LED6, horn lines, fire
alarm outputs
– –
10 "Alarm" zone 3 = Activate LED6, horn lines
12
"Alarm" zone 1 + 2 + 3 = "Activated"
"Alarm" zone 1 or 2 or 3 or any two zones = "Fire alarm"
KEY15
▼
13
"Alarm" zone 3 = Activate fire control lines, LED6, horn lines
Processing as "Air sampling system" (earliest warning)