11.6.13 Step 13, change the parameters of the operator interface
Change the processing of "Fire alarm condition"
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
1 (default)
“Fire alarm” also in state “Manual only”:
LED6 = lit in steady mode, LED7 = flashing fast
Active: Horns, monitored control lines and outputs programmed as
activated on fire alarm condition
KEY13
2
No “Fire alarm” in state “Manual only”:
LED6 = lit in steady mode, LED7 = OFF
Not active: Horns, monitored control lines and outputs programmed
as activated on fire alarm condition
Change the function of the key "Silence buzzer" (KEY15)
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
3 (default)
Only for "Silence buzzer" in state "Fire alarm"
KEY13
4 For "Silence buzzer" and "Silence Re-sound horn" in state "Fire alarm"
Enable the function "Reminder beep"
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
5 (default)
No reminder beep
KEY14
6 Buzzer sounds every 4 min for 1 sec in case of "Fault" or "Disabled"
Enable the function "Fault to be reset"
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
7 (default)
Faults must not be reset
KEY14
8 All faults must be reset
Enable the function "RT-alarm + RT-fault suppressed on access level 2"
Zone 1 Zone 2
Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
9 (default)
No blocking
KEY15
10 "RT-alarm" and "RT-fault" disabled on state "Access level 2 enabled"
Enable the function "Reset via control input 1 suppressed upon RT-alarm"
Zone 1 Zone 2
Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
11 (default)
Not blocked
KEY15
12 Blocked on state "RT-alarm"
Suppress the "Battery fault"
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
13 (default)
Battery fault not suppressed
KEY16
14 Battery fault suppressed
Change the active mode of the buzzer in state "Emergency hold/abort"
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
15 (default)
1 sec beep with begin and end of state "Emergency hold/abort"
KEY16
16 Active until key "Silence buzzer" is pressed