Programming the user functions
82
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.8 Step 8, change the function of the monitored input 3
Change the function of the monitored input 3
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Function "Emergency abort"
In state "Activated":
"Active 1" = ON = Activated time is stopped
LED26 lights up
Horn turns to "Hold/Abort" tone
"Active 1" cancelled = Abort remains active until reset
1 (default)
In state "Normal":
"Active 1" = ON = LED26 lights up
Block the activated process. When new alarm
happens, system enters
"
Fire alarm
"
state
"Active 1" cancelled = Abort remains active until reset
– – – – – –
Function "Emergency hold"
In state "Activated":
"Active 1" = ON = Activated time is stopped
LED26 lights up
Horn turns to "Hold/Abort" tone
"Active 1" cancelled = Activated time restarts
LED26 switches off
Horn turns to "Activated" tone
2
In state "Normal":
"Active 1" = ON = LED26 lights up
Block the activated process. When new alarm
happens, system enters "Fire alarm" state
"Active 1" cancelled = Return to "Normal state"
– – – – –
Function "Block"/"Emergency hold" 1
In state "Activated" by detector:
"Active 1" = ON = Activated time is stopped
LED26 lights up
Horn turns to "Hold/Abort" tone
"Active 1" cancelled = Activated time restarts
LED26 switches off
Horn returns to "Activated" tone
"Active 2" = ON = No reaction
In state "Activated" by manual activation:
"Active 1" = ON = No reaction
"Active 2" = ON = No reaction
3
In state "Normal":
"Active 1" = ON = Autom. & Man. blocked
"Active 1" cancelled = Blocking disabled
"Active 2" = ON = Manual only
"Active 2" cancelled = Blocking disabled
–
– – – –
Function "Block"/"Emergency hold" 2
In state "Activated" by detector:
"Active 1" = ON = Activated time is stopped
LED26 lights up
Horn turns to "Hold/Abort" tone
"Active 1" cancelled = Activated time restarts
LED26 switches off
Horn returns to "Activated" tone
In state "Activated" by manual activation:
"Active 1" = ON = No reaction
KEY13
▼
4
In state "Normal":
"Active 1" = ON = Manual only
"Active 1" cancelled = Blocking disabled
– –
– – –
"Active 1" = 680Ω, “Active 2" = 1k2