11.4.2 Description of the default settings
Default settings for standard applications are based on EN54-2 and EN12094-1.
Step Function Default
setting
Default value
Change the activated time of control line 4 7 Activated time 30 seconds 1
Change the function of control line 5 14 Active in state "Activated" but activated time 0 seconds
Processing as "Actuator"
Change the flooding time of control line 4 1 Flooding time 30 seconds 2
Change the flooding time of control line 5 6 Flooding time 30 seconds
Change the function of contact 1 1 Active during "Released" to "Reset" state
Change the function of contact 3 5 Active with "Fire alarm" to "Reset" state
8 Active during "Fault" to "Silence Buzzer" state Change the function of contact 2
10 Immediate triggering
12 LED9: Active only in "RT-alarm" state Change the function of LED9 (Remote
transmission) and LED6 (Fire alarm)
15 LED6: Active on Alarm Z1 or Z2 or Z3
3
Change the function of control line 2 17 Active on state "RT-alarm" to "Reset"
Processing as "RT-alarm"
Change the function of monitored input 1 1 State "Active 1" (680) = "Released"
State "Active 2"(1k2) = "Loss of agent"
State "Open" or "Short circuit" = "Fault"
Suppress the fault indication if state "Released" is
not reported
4 Fault if state "Released" is not reported within 30sec after control
line 4 has been activated
4
Change the function of monitored input 2 6 State "Active 1" (680) = "Mech. Blocked"
State "Active 2" (1k2) = "Normal" (not mech. blocked)
State "Active 1 + 2" or "Inactive 1 + 2" = "Fault" (LED2 flashing)
State "Open" or "Short circuit" = "Fault"
1 State "Fire alarm" = continuous
5 State "Activated" = pulsating fast and pulsating slow in state
"Emergency hold or abort"
Change the active mode of control line 1
9 State "Released" = pulsating
Change the active period of control line 1 11 Active until "Silence Re-sound Horn" and "Reset"
15 State "Fire alarm" = not activated
18 State "Activated" = continuous
5
Change the active mode and active period of
control line 3
20 State "Released" = continuous until "Reset"
Enable "Alarm verification" function of detector
zones 1 and 2
1 No alarm verification
Enable "Alarm verification" function of detector zone
3
3 No alarm verification
6
Enable "Alarm verification" function of detector zone
4
5 No alarm verification
Deleted 1 Not applicable
Deleted 7, 9 Not applicable
7
Deleted 11 Not applicable
In state "Activated":
State "Active 1" (680) = LED26 lights up
Activated time is stopped
Horn turns to "Hold/Abort" tone
State "Active 1" cancelled = Abort remains active until reset
Change the function of monitored input 3 1
In state "Normal":
State "Active 1" (680) = LED26 lights up
Block the activated process. When
new alarm happens, system enters
fire alarm state and horn turns to
"Hold/Abort" tone
State "Active 1" cancelled = Abort remains active until reset
Suppress "Reset" upon stopped activated time by
the monitored input 3
8 Function "Reset" available
8
Change the fault processing of the monitored input
3
10 State "Short circuit" and "Open" = "Fault" + "Emergency
hold/abort" state