Description of the default settings (continuation)
Step Function Default
setting
Default value
Change the reaction after "Reset" of the detector
zones 1 and 2
1 Alarm <15 seconds after "Reset" = new line alarm
Change the reaction after "Reset" of the detector
zone 3
3 Alarm <15 seconds after "Reset" = new line alarm
Change the reaction after "Reset" of the detector
zone 4 (manual release)
6 Alarm <15 seconds after "Reset" = line fault
Change the reaction after "Reset" of the monitored
input 1
8 State "Active 1" <15 seconds after "Reset" = "Fault" and LED8
"Released" activated
Interlock the "Reset" function if executed via control
input 1
10 In "Fire alarm" state: Reset possible only after "Silence buzzer"
In "Activated" and "Released" states: Reset possible only after
"Silence horn" and after the flooding time of control line 4 has
elapsed
9
Interlock the "Reset" function 11 Reset always possible
Change the indication of the blocking states 1 Indication "Mode Standard":
LED3 = not used
LED4 = "Manual only"
LED5 = "Autom. & Man. Blocked"
10
Change active mode of indicator "Released" (LED8)
3 Flashing in state "Released"
Change the function of the detector zones 1 and 2 1 "Alarm" zone 1 and zone 2 = "Activated"
"Alarm" zone 1 or zone 2 = "Fire alarm"
Change the line fault processing of the detector
zones 1 and 2
6 State "Open" and "Short circuit" = "Fault"
11
Change the function of the detector zone 3 9 "Alarm" zone 3 = activate fire controls, RT-alarm (if step 3 option
3 or 4), fire alarm (LED6), horn lines, fire alarm outputs
Change the basic code for access level 2 1 Access code "4233" defined 12
Change the access level for the function "Silence
buzzer"
4 Can always be silenced
Change the processing of "Fire alarm condition" 1 ”Fire alarm” also in state “Manual only” = activate LED6 (lit), LED7
(fast), horn lines, monitored control lines and outputs programmed
as activated on fire alarm condition
Change the function of the key "Silence buzzer"
(KEY15)
3 Key15 only for "Silence buzzer" in state "Fire alarm"
Enable the function "Reminder beep" 5 No reminder beep
Enable the function "Fault to be Reset" 7 "Fault" must not be reset
Enable the function "RT-alarm + RT-fault
suppressed on access level 2"
9 No blocking
Enable the function "Reset via control input 1
suppressed upon RT-alarm"
11 Control input 1 not blocked
Suppress the "Battery fault" 13 Battery fault not suppressed
13
Change the active mode of the buzzer in state
"Emergency hold/abort"
15 1 sec beep with begin and end of state "Emergency hold/abort"
14 Change the fault delay upon "Mains failure" 3 Delay = 10 minutes
Change the function of control input 2 1 Initiate function "Silence buzzer"
Change the function of control input 3 8 Enable state "Fault"
15
Change the function of control input 4 15 Release "Silence Re-sound Horn" function
1 Active on "Activated" and "Released" states Change the function of driver output 2
9 Output "Disable/Enable" with Key11 “Disable Fire control”
10 Active on "Emergency hold/abort" state Change the function of driver output 8
18 Output "Disable/Enable" with Key11 “Disable Fire control”
16
Change the function of driver output 1 20 Output "Disable/Enable" with Key11 “Disable Fire control”