5.7 Technical data
Supply
Mains supply 115/230 V
A
.
C
.; +10 % / -15 %
Power consumption 20 ... 150 VA
Secondary supply (current on low voltage side) max. 3.5 A
System supply voltage 20 ... 28 V
D
.
C
.
Ripple max. 400 mV
Indication after total loss of power yes, selectable by additional cable connection
Emergency power supply
Operating time max. 23 h with 4.5 Ah batteries,
max. 38 h with 7.2 Ah batteries
Battery capacity 2 x 12 V / 4.5 Ah or 7.2 Ah (V0 or V1 or V2)
Quiescent current, nominal (battery operation) 132 mA (after fault relay dropped)
Additional power consumption on alarm approx. 50 mA (without power for peripheral devices)
Battery low charge shut-off <19.8 V
D
.
C
.
Temperature compensation of charging voltage
Yes
Detector lines
Detector lines
– 'LIN 1', 'LIN 2'
– 'LIN 3'
– 'LIN 4'
for detectors within extinguishing area
for detectors outside of extinguishing area
for manual activation button
Line type for conventional detectors
Number of detectors per line max. 32 (max. KLK 32)
Compatible device series Siemens (AlgoRex DS11xx, DC1192, Sinteso
FDOOT241-9, FDL241-9, FDF221-9, FDF241-9)
Standard (SynoLINE 300C)
Operating voltage/quiescent current 18 … 22 V / max. 3.2 mA
Line resistor/line capacity
– Siemens and Synova types
≤ 80 Ω / ≤ 1 µF (if “Break” = “alarm”: the line resistance
should be lower than 50 Ω)
Alarm criteria
– Siemens type / Synova type
17.5 … 39 mA and > 5.1 V / 17…83.6 mA
Alarm activation
– Siemens type / Synova type
Resistor 820 Ω or Z diode 5.6 Volts / Resistor 820 Ω
Line termination element Resistor 3k3
Inputs
Monitored inputs 1 to 3
– Activation resistor
For Active 1 state: Resistor 680 Ω (single device)
Element XCE1002 (multiple devices,
only for monitored input 3)
For Active 2 state: Resistor 1k2
– Line termination Resistor 3k3
– Line resistance max. 50 Ω
Control inputs 1 to 4 (not monitored)
– Activation
24 V positive potential switched via contact
Outputs
Monitored control lines 1, 2 and 3
– Voltage/current in active state
– Line termination
24 V/max. 500 mA (principle of reverse polarity)
Termination element FCE1002
Monitored control lines 4 and 5
– Voltage/current in active state
– Line termination
– Line monitoring
– Admissible external load
24 V/max. 2 A
None
Resistance of external load is monitored
Pyrotechnical actuators >1 Ω / Solenoid 15…850 Ω
Potential-free contacts
– Number / Contact rating
5 / max. 1 A/30 V
D
.
C
.
Driver outputs
– Number / Rating
8 / max. 40 mA/24 V
D
.
C
.
Connections
Detector lines, Inputs, Outputs
– Design / Wire cross-section
Screw-type terminals / 0,2 ... 1.5 mm
2
Mains voltage
– Design / Wire cross-section
Screw-type terminals / 1 ... 2.5 mm
2
Environmental conditions
Operating temperature -5 ... +40 °C (Class A)
Storage temperature
Humidity (no condensation) max. 93% rel. at T = 40 ±2 °C
Protection rating IP 30
Mechanical data
Housing type Metal chassis with plastic cover
Colour Cover RAL 9003 white
Dimensions (W x H x D) 370 x 286 x 90 mm
Weight 6.600 kg (without batteries)
Standards and Approvals
Standards EN 12094-1, EN 54-2, EN 54-4
Approvals Notified body N° 1116 : CNPP – France