Programming the user functions
79
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.4 Step 4, change the function of the monitored inputs 1 and 2
Change the function of the monitored input 1
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
1 (default)
State "Active 1" = "Released"
State "Active 2" = "Loss of agent"
State "Open" or "Short circuit" = "Fault"
–
2 State "Active 1" = "Released"
State "Inactive 2" = "Loss of agent"
State "Open" or "Short circuit" = "Fault"
KEY13
▼
3 State "Active 1" = no effect
State "Active 2" = "Loss of agent"
State "Open" or "Short circuit" = "Fault"
State "Released" is indicated as soon as the activated time has
elapsed
"Active 1" = 680Ω, “Active 2" = 1k2
Suppress the fault indication if state "Released" is not reported
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
4 (default)
Fault if state "Released" is not reported within 30 sec after control line
4 has been activated
–
KEY13
▼
5 No fault reported
Change the function of monitored input 2
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
6 (default)
State "Active 1" + "Inactive 2" = "Mech. blocked"
State "Inactive 1" + "Active 2" = "Normal" (not blocked)
State "Active 1+2" or "Inactive 1+2" = "Fault" (LED2 flashing)
State "Open" or "Short circuit" = "Fault"
– –
7 Same as option 6 but with "Autom. & Man. blocked" on state "Active
1" + "Inactive 2"
–
8 State "Active 1" = "Autom. & Man. blocked"
State "Active 2" = "Manual only"
State "Active 1+2" = "Autom. & Man. blocked"
State "Inactive 1+2" = "normal"
State "Open" or "Short circuit" = "Fault"
Inoperative in state "Activated"
–
9 State "Active 1" = start "Activated time"
State "Active 2" = no effect
State "Open" or "Short circuit" = "Fault"
KEY14
▼
10 State "Active 1 + Inactive 2" = "Loss of agent"
State "Inactive 1 + Active 2" = "Normal"
State "Inactive 1+2" = "Loss of agent"
State "Open" or "Short circuit" = "Fault"
–
"Active 1" = 680Ω, “Active 2" = 1k2