EasyManua.ls Logo

Siemens XC1003-A - Checking the remote transmission of alarm

Siemens XC1003-A
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Structure and function
24
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
5.3.2 Adjusting elements of the XCM1001-2 upper main board
This board contains parameters for:
Permanently activate of operating level 2
Change the contact type NO/NC
Disable activation of the buzzer
Activate the calibration procedure for control lines 4 and 5
Fig. 12 Adjusting elements of the XCM1001-2 upper main board
Ref. Function
Jumper
pos.
Parameter
ON Permanent access PU1 Operating access level 2
OFF Access only using code (factory setting)
ON Right NO contact (factory setting) PU2 Potential-free contact "RT-alarm"
(programmable in step 3/option 1-4)
ON Left NC contact
ON Right NO contact (factory setting) PU3 Potential-free contact "RT-fault"
(programmable in step 3/ option 8-11)
ON Left NC contact (schematic in power off state)
ON Right NO contact (factory setting) PU4 Potential-free contact "Fire alarm"
(programmable in step 3/ option 5-6)
ON Left NC contact
ON Right NO contact (factory setting) PU5 Potential-free contact "Manual only"
ON Left NC contact
ON Right NO contact (factory setting) PU6 Potential-free contact "Autom. & Man.
blocked"
ON Left NC contact
ON Activated (factory setting) PU7 Temporary disabling of buzzer
OFF Not activated (only for servicing)
PU8 Factory test OFF (factory setting)
PU9 Factory test OFF (factory setting)
ON Calibration activated PU10
Calibrating the control lines 4 and 5
(details see chapter 10.6)
OFF Calibration not activated (factory setting)

Table of Contents

Other manuals for Siemens XC1003-A

Related product manuals