Programming the user functions
76
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.1 Step 1, changing the activated time and function of control lines 4/5
Change the activated time of control line 4
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
1 Activated time 0 seconds
2 Activated time 5 seconds
3 Activated time 10 seconds
4 Activated time 15 seconds
5 Activated time 20 seconds
6 Activated time 25 seconds
7 (default)
Activated time 30 seconds
8 Activated time 35 seconds
9 Activated time 40 seconds
10 Activated time 45 seconds
11 Activated time 50 seconds
12 Activated time 55 seconds
KEY13
13 Activated time 60 seconds
Change the function of control line 5
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
14 (default)
Active in state "Activated" but activated time 0 seconds
Processing as "Actuator"
15
Active same as control line 4
Processing as "Actuator"
16
Active same as control line 1 (horn)
Processing as "Horn"
17
Active in state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 options 9, 12 or 13), "Activated" and "Released"
Processing as "Fire Control"
18
Active in state "Mech. blocked"
Processing as " Warning Panel"
19
Active in state "Auto. & Man. blocked"
Processing as "Warning Panel"
20
Activated in state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is
programmed in step 11 options 9, 10, 12 or 13) and "Activated"
Processing as "Horn"
KEY14
21
Active in state "Manual only" or "Autom. & Man. Blocked"
Processing as "Warning Panel"
Lit
Pulsated fast
Pulsated slow