Programming the user functions
76
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.1 Step 1, changing the activated time and function of control lines 4/5
Change the activated time of control line 4
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
1 Activated time 0 seconds – – – – – –
2 Activated time 5 seconds
– – – – –
3 Activated time 10 seconds
– – – –
4 Activated time 15 seconds – –
– – –
5 Activated time 20 seconds – – –
– –
6 Activated time 25 seconds – – – –
–
7 (default)
Activated time 30 seconds – – – – –
8 Activated time 35 seconds
– – – – –
9 Activated time 40 seconds –
– – – –
10 Activated time 45 seconds – –
– – –
11 Activated time 50 seconds – – –
– –
12 Activated time 55 seconds – – – –
–
KEY13
▼
13 Activated time 60 seconds – – – – –
Change the function of control line 5
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Active in state "Activated" but activated time 0 seconds
Processing as "Actuator"
– –
15
Active same as control line 4
Processing as "Actuator"
–
16
Active same as control line 1 (horn)
Processing as "Horn"
–
17
Active in state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 options 9, 12 or 13), "Activated" and "Released"
Processing as "Fire Control"
18
Active in state "Mech. blocked"
Processing as " Warning Panel"
19
Active in state "Auto. & Man. blocked"
Processing as "Warning Panel"
20
Activated in state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is
programmed in step 11 options 9, 10, 12 or 13) and "Activated"
Processing as "Horn"
KEY14
▼
21
Active in state "Manual only" or "Autom. & Man. Blocked"
Processing as "Warning Panel"
–