Programming the user functions
89
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.16 Step 16, change the function of the driver outputs 2, 8 and 1
Change the function of driver output 2
Zone 1 Zone 2
Zone 3 Zone 4
Select Option Function
Red
1 (default)
Active on "Activated" and "Released" – –
2
Active on "Fire alarm" Z1 or Z2 or Z3 if zone 3 is programmed in step
11 option 12 or 13
–
3 Active on "Activated" –
4
Active on normal operation
Inactive on "Fault", "Fire alarm" Z1 or 2 or Z3, "Activated", "Released"
Processing as door magnetic
–
5 Active on "Fault" on control line 5 –
6 Active in "Normal operation" (microcomputer working)
KEY13
▼
7 Active on "Mech. blocked"
8 Output not "Disable/Enable" with key "Disable/Enable Fire control"
–
KEY14
▼
9 (default)
Output "Disable/Enable" with key "Disable/Enable Fire control" (*)
(*) not allowed on state "Activated" and "Released"
Change the function of driver output 8
Zone 1 Zone 2
Zone 3 Zone 4
Select Option Function
Red
Active on "Emergency hold/abort" – –
11 Active on "Autom. & Man." (normal operation)
–
12 Active on "Fault power supply" –
13 Active on «Loss of agent»
–
14 Active on "Detector test" –
15 Active on "Alarm" zone 3 until "Reset"
KEY15
▼
17 Active in status isn’t “normal operation” (any indication on the XC10)
Output "Disable/Enable" with key "Disable/Enable Fire control" (*)
–
KEY16
▼
19 Output not "Disable/Enable" with key "Disable/Enable Fire control"
(*) not allowed on state "Activated" and "Released"
Change the function of driver output 1
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Output "Disable/Enable" with key "Disable/Enable Fire control" (*)
–
KEY16
▼
21 Output not "Disable/Enable" with key "Disable/Enable Fire control"
(*) not allowed on state "Activated" and "Released"