Programming the user functions
78
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.3 Step 3, change the function of the remote transmission
Change the function of contact 1
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
1 (default)
Active during "Released" to "Reset" state
2 Active during "Activated" or "Released" to "Reset" state
3
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 option 9, 10 or 12) to "Reset" state
KEY13
4
Active during "Fire alarm” (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 option 9 or 10 or 12) or "Activated" or "Released" to "Reset"
state
Change the function of contact 3
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
5 (default)
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 option 9 or 12) to "Reset" state
6
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 option 9 or 12) or "Activated" to "Reset" state
KEY13
7 Active during “Emergency hold/abort” until the cause is eliminated
Change the function of contact 2
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
8 (default)
Active during "Fault" to "Silence buzzer" state
9
Active during "Fault" state until the cause is eliminated and "Silence
buzzer"
10 (default)
Immediate triggering
KEY14
11 3 minutes delay in "Buzzer not silenced" state (*)
Change the function of LED9 (Remote transmission) and LED6 (Fire alarm)
Zone 1 Zone 2
Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
12 (default)
LED9: Active only in "RT-alarm" (*) state
13 LED9: Active in "RT-alarm" (*) and "RT-fault" (**) state
14 LED9: Inoperative (LED23, LED25 and KEY12 without function)
15 (default)
LED6: Active on Alarm Z1 or Z2 or Z3
KEY15
16 LED6: Active on "Activated" if activated is initiated by detectors
(*) Function dependent on option 1 to 4
(**) Function dependent on option 8 and 9
Change the function of control line 2
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
17 (default)
Active on state "RT-alarm" to "Reset" (*)
Processing as "RT-alarm"
18 Active on state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed
in step 11 option 9, 12 or 13), "Activated" and "Released" to "Reset"
Processing as "Fire control"
19 Active on state "Activated" and "Released" to "Reset"
Processing as "Fire control"
20 Active on state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed
in step 11 option 9, 10, 12 or 13), "Activated" and "Released" to
"Silence Re-sound horn" or "Reset"
Processing as "Horn"
21 Active on state "Activated" and "Released" to "Silence Re-sound
Horn" or "Reset"
Processing as "Horn"
22 Active on state "Mech. blocked"
Processing as "Warning panel"
23 Active on state "Autom. & Man. blocked"
Processing as "Warning panel"
KEY16
24 Active on state "Manual only" or "Autom. & Man. blocked"
Processing as "Warning panel"
(*) Function of dependent on option 1 to 4