Programming the user functions
78
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.3 Step 3, change the function of the remote transmission
Change the function of contact 1
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
1 (default)
Active during "Released" to "Reset" state –
2 Active during "Activated" or "Released" to "Reset" state
3
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 option 9, 10 or 12) to "Reset" state
KEY13
▼
4
Active during "Fire alarm” (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 option 9 or 10 or 12) or "Activated" or "Released" to "Reset"
state
Change the function of contact 3
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
5 (default)
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 option 9 or 12) to "Reset" state
–
6
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
step 11 option 9 or 12) or "Activated" to "Reset" state
KEY13
▼
7 Active during “Emergency hold/abort” until the cause is eliminated
Change the function of contact 2
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
8 (default)
Active during "Fault" to "Silence buzzer" state –
9
Active during "Fault" state until the cause is eliminated and "Silence
buzzer"
Immediate triggering –
KEY14
▼
11 3 minutes delay in "Buzzer not silenced" state (*)
Change the function of LED9 (Remote transmission) and LED6 (Fire alarm)
Zone 1 Zone 2
Zone 3
Zone 4
Select Option Function
Red
LED9: Active only in "RT-alarm" (*) state –
13 LED9: Active in "RT-alarm" (*) and "RT-fault" (**) state
14 LED9: Inoperative (LED23, LED25 and KEY12 without function)
15 (default)
LED6: Active on Alarm Z1 or Z2 or Z3 –
KEY15
▼
16 LED6: Active on "Activated" if activated is initiated by detectors
(*) Function dependent on option 1 to 4
(**) Function dependent on option 8 and 9
Change the function of control line 2
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Active on state "RT-alarm" to "Reset" (*)
Processing as "RT-alarm"
– –
18 Active on state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed
in step 11 option 9, 12 or 13), "Activated" and "Released" to "Reset"
Processing as "Fire control"
–
19 Active on state "Activated" and "Released" to "Reset"
Processing as "Fire control"
–
20 Active on state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed
in step 11 option 9, 10, 12 or 13), "Activated" and "Released" to
"Silence Re-sound horn" or "Reset"
Processing as "Horn"
–
21 Active on state "Activated" and "Released" to "Silence Re-sound
Horn" or "Reset"
Processing as "Horn"
–
22 Active on state "Mech. blocked"
Processing as "Warning panel"
23 Active on state "Autom. & Man. blocked"
Processing as "Warning panel"
KEY16
▼
24 Active on state "Manual only" or "Autom. & Man. blocked"
Processing as "Warning panel"
(*) Function of dependent on option 1 to 4