Programming the user functions
77
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.2 Step 2, change the flooding time (active period) of control lines 4/5
Change the flooding time of control line 4
Zone 1 Zone 2
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
Red
Yel.
Red
Yel.
1 (default)
Flooding time 30 seconds
2 Flooding time 60 seconds
3 Flooding time 90 seconds
4 Flooding time 120 seconds
KEY13
5 Flooding time to "Reset"
Change the flooding time of control line 5
Zone 3 Zone 4
Select Option Function
Red
Yel.
Red
Yel.
6 (default)
Flooding time 30 seconds (*)
7 Flooding time 60 seconds (*)
8 Flooding time 90 seconds (*)
9 Flooding time 120 seconds (*)
KEY14
10 Flooding time to "Reset"
(*) Only relevant if control line 5 is set to option 14 or 15 in
programming step 1. With option 14, control line 5 is already
activated with “Activated” but the selected flooding time starts only
counting with the activation of control line 4.