Programming the user functions
81
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.6 Step 6, enable the "Alarm verification" function
Enable "Alarm verification" function of detector zones 1 and 2
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
1 (default)
No alarm verification –
KEY13
▼
2
Twice line alarm within 60 seconds = Alarm
After first line alarm = automatic reset and short flash up of zone LED
Enable "Alarm verification" function of detector zone 3
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
3 (default)
No alarm verification –
KEY13
▼
4
Twice line alarm within 60 seconds = Alarm
After first line alarm = automatic reset and short flash up of zone LED
Enable "Alarm verification" function of detector zone 4
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
5 (default)
No alarm verification –
KEY14
▼
6
Twice line alarm within 60 seconds = Alarm
After first line alarm = automatic reset and short flash up of zone LED
11.6.7 Step 7, define the function of the yellow key (KEY8)
Key 8 is not accessible with XC1003-A.
Define the function of the yellow key (KEY8)
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
1 (default)
Deleted – – – – –
2 Not to be used
– – – –
3 Not to be used –
– – –
4 Not to be used – –
– –
5 Not to be used – – –
–
KEY13
▼
6 Not to be used – – – –
Change the operating access of the yellow key (KEY8)
Zone 1 Zone 2
Zone 3 Zone 4
Select Option Function
Red
7 (default)
Deleted –
KEY14
▼
8 Not to be used
9 (default)
Deleted –
KEY15
▼
10 Not to be used
Suppress "Reset" upon stopped activated time by the yellow key (KEY8)
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Deleted –
KEY16
▼
12 Not to be used