Programming the user functions
84
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
11.6.9 Step 9, change the parameters to the "Reset" function
Change the reaction after "Reset" of the detector zones 1 and 2
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
1 (default)
Alarm <15 seconds after "Reset" = New line alarm –
KEY13
▼
2 Alarm <15 seconds after "Reset" = Line fault
Change the reaction after "Reset" of the detector zone 3
Zone 1
Zone 2 Zone 3 Zone 4
Select Option Function
Red
3 (default)
Alarm <15 seconds after "Reset" = New line alarm –
KEY13
▼
4 Alarm <15 seconds after "Reset" = Line fault
Change the reaction after "Reset" of the detector zone 4 (manual release)
Zone 1
Zone 2
Zone 3 Zone 4
Select Option Function
Red
5 Alarm <15 seconds after "Reset" = New line alarm –
KEY14
▼
6 (default)
Alarm <15 seconds after "Reset" = Line fault
Change the reaction after "Reset" of the monitored input 1
Zone 1 Zone 2
Zone 3
Zone 4
Select Option Function
Red
7
State "Active 1" <15 seconds after "Reset" = "Released" enabled
again (LED8 flashing)
–
KEY15
▼
8 (default)
State "Active 1" <15 seconds after "Reset" = "Released" not enabled
(LED8 in steady mode + "Fault")
"Active 1" = 680Ω
Interlock the "Reset" function if executed via control input 1
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
9 Reset always possible –
KEY16
▼
10 (default)
In case of "Fire alarm": Reset possible only after "Silence buzzer"
In case of "Activated" and "Released": Reset possible only after
"Silence horn" and after the flooding time of control line 4 has elapsed
Interlock the "Reset" function
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Reset always possible –
KEY16
▼
12
Reset not possible if:
–
zone 4 is on state "Alarm"
–
monitored input 1 is on state "Active 1"
–
control line 1 (horn) is in state "Active"