Programming the user functions
83
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
(Programming Step 8, continued)
Change the function of the monitored input 3
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
Function "Emergency hold" 2
In state "Activated":
"Active 1" = ON = Activated time continue, but stop at beginning
of released
LED26 lights up
Horn turns to "Hold/Abort" tone
"Active 1" cancelled = Activated time continue and if activated time is
elapsed state released occurs
Horn returns to "Activated" tone
"Active 2" = ON = No reaction
5
In state "Normal":
"Active 1" = ON = Block the activated process. When new alarm
happens, system enters activated state
LED26 lights up
"Active 1" cancelled = Return to normal state
"Active 2" = ON = Manual only
"Active 2" cancelled = Blocking disabled
– – –
– –
Function "Block" 1
In state "Activated":
"Active 1" = ON = No reaction
6
In state "Normal":
"Active 1" = ON = Manual only
"Active 1" cancelled = Blocking disabled
– – – –
–
Function "Block" 2
In state "Activated":
"Active 1" = ON = No reaction
"Active 2" = ON = No reaction
KEY13
▼
7
In state "Normal":
"Active 1" = ON = Autom. & Man. blocked
"Active 1" cancelled = Blocking disabled
"Active 2" = ON = Manual only
"Active 2" cancelled = Blocking disabled
– – – – –
"Active 1" = 680Ω, "Active 2" = 1k2
Suppress "Reset" upon stopped activated time by the monitored input 3
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
8 (default)
Function "Reset" available –
KEY14
▼
9 Function "Reset" suppressed
Note: Do not select option 1 with option 9 together because Reset will
never be allowed
Change the fault processing of the monitored input 3
Zone 1 Zone 2 Zone 3
Zone 4
Select Option Function
Red
State "Short circuit" and "Open" = "Fault" + "Emergency hold/abort" –
KEY15
▼
11 State "Short circuit" and "Open" = "Fault"